Installation Details:
Date:                        Ref:                                  User Code:                                    
Name:                                                              Default Code:                                 
Address:                                                           Engineer Code:                              
Tel:                               Fax:                             Panel Make/Model:                        

  1: MAINS PHASE NEUTRAL TEST. AC voltage between Live and Neutral.
This should measure between 220 - 250VAC.
MAINS PHASE EARTH TEST: AC voltage between Live and Earth.
This should be the same as the previous reading.
MAINS NEUTRAL EARTH TEST: AC voltage between Neutral and Earth.
This reading should not exceed 1.2VAC.

  2:
POWER SUPPLY TEST: Transformer AC voltage output.
This should measure between 14 - 21VAC.
  3:
POWER SUPPLY CURRENT NORMAL TEST: AC current used by system when unset.
Measure with meter in series with the transformer output.
  4:
POWER SUPPLY CURRENT IN ALARM TEST: AC current used by system when in alarm. As step 3.
  5:
INDUCED AC TEST: AC voltage between DC+ and earth.
AC noise should not exceed 1.2 volts max.
  6:
BATTERY CHARGING VOLTAGE TEST: DC voltage at battery terminals.
Measure with charge leads connected to the battery.
  7:
PANEL AUXILIARY DC VOLTAGE TEST: DC voltage supply to detectors.
Should be within ±1volt of the battery charging voltage.
  8:
BATTERY FLOAT CHARGE TEST: DC mA current flowing through battery. Should fall from a double mA figure to a single mA figure within 30 seconds.
  9:
BATTERY SYSTEM CURRENT NORMAL TEST: DC current used by system when unset.
Ideally, not more than 5% of the batteries Ah capacity.
10:
BATTERY SYSTEM CURRENT IN ALARM TEST: DC current used by system when in alarm.
Ideally, not more than 10% of the batteries Ah capacity.
11: BATTERY TEST: Record Temperature, Voltage                                °C  DCV Ah
and Capacity available. Replace battery when
reading
falls below 65% of Ah capacity.
12:
CIRCUIT RESISTANCE TESTS: Record all circuit resistances. Circuits must be removed from control panel before testing.
13:
CIRCUIT EARTH LEAKAGE TEST: Check for resistance between zone, tamper and earth. Test with meter on highest Meg Ohm range.
14:
BELL TAMPER RETURN TEST: Record resistance between 0Volt and removed tamper return.
Check for stable resistance. Ring bell to induce vibration.
15:
PANEL ZONE WALKTEST: Walktest all detection zones to confirm operation.
Check each circuit operates normally, especially after lightning.
16:
SELF-ACTIVATING BELL TEST: Remove hold-off voltage to confirm operation. Replace if defective.
17:
BELL & STROBE TEST: Activate bell and strobe to confirm operation. Replace if defective.
18:
COMMUNICATOR TEST: Activate communicator to confirm operation. Confirm correct operation with Alarm Receiving Centre.
19:
WIRING AND CONNECTIONS: Check panel for incorrect or loose wiring connections. Check all cables are marked and connected correctly.
20:
DETECTOR VOLTAGE TEST: Check voltage at furthest detector is above 13VDC. Low or unstable DC voltage at the detector is a main cause of false alarms.